Panel Schedule Builder

A
Voltage

Circuits

Total Connected Load3,300 W
Phase A Load1,800 W
Phase B Load1,500 W
Load Imbalance18.2%
Panel Utilization6.9%
Circuit Count2

Warnings

  • !Load imbalance of 18.2% exceeds recommended 10% maximum

Circuit Directory

#DescriptionBreakerPolesPhaseLoad (W)
1Kitchen20A1PA1,800
2Living Room20A1PB1,500

A panel schedule documents every circuit in a distribution panel and, just as importantly, shows whether the load is balanced across phases. This builder distributes each circuit's watts across its assigned phase legs, totals the per-phase load, computes the imbalance between the heaviest and lightest legs, and tracks panel utilization, flagging conditions that violate good practice.

Formula

Imbalance% = (Pmax − Pmin) / Pavg × 100

Pmax
Watts on the most heavily loaded phase leg
Pmin
Watts on the least loaded (non-zero) phase leg
Pavg
Average watts across the loaded phase legs
Imbalance%
Percent difference used to flag unbalanced panels (10% recommended maximum)

How it works

  1. Set the panel name, main breaker amps, and voltage system (120/240 single-phase or 120/208 three-phase), then add circuits with a description, breaker size, pole count, load in watts, and phase assignment (A, B, C, or a multi-phase pairing).
  2. Each circuit's watts are split across the legs it occupies: a single-phase circuit loads one leg, a two-phase pairing splits evenly across two legs, and a three-phase circuit divides across all three.
  3. The tool sums each phase, computes the imbalance percentage from the spread between legs, and reports panel utilization against capacity, raising warnings when imbalance exceeds 10%, utilization passes 80%, or a leg exceeds the main rating.

Worked example

A 200 A, 120/240 V panel with a 1440 W lighting circuit on A, a 1200 W receptacle circuit on B, a 4800 W two-pole AC circuit on AB, and a 1500 W kitchen circuit on A.

  1. Phase A: 1440 + (4800 ÷ 2) + 1500 = 1440 + 2400 + 1500 = 5340 W.
  2. Phase B: 1200 + (4800 ÷ 2) = 1200 + 2400 = 3600 W.
  3. Average of the two legs: (5340 + 3600) ÷ 2 = 4470 W.
  4. Imbalance: (5340 − 3600) ÷ 4470 × 100 ≈ 38.9%. Total connected load = 8940 W; utilization = 8940 ÷ (200 × 240) ≈ 18.6%.

Phase A 5340 W, Phase B 3600 W, imbalance ≈ 38.9% (exceeds the 10% guideline), utilization ≈ 18.6%.

Frequently asked questions

Why does load balance between phases matter?
An unbalanced panel overloads one leg while leaving another underused, causing higher neutral current, extra heating, and wasted capacity. Keeping the imbalance within about 10% improves efficiency, reduces voltage variation between legs, and makes full use of the panel rating.
How is panel utilization calculated?
Utilization is the total connected watts divided by the panel's capacity. For a 120/240 V panel the capacity is main amps × 240; for a 120/208 V three-phase panel it is main amps × 208 × √3. Staying under 80% leaves headroom for growth and continuous loads.
What does a two-pole or three-pole assignment do to the load?
A multi-pole breaker spans more than one phase leg, so its load is shared. This tool splits a two-pole (AB, BC, AC) load evenly across its two legs and a three-pole (ABC) load across all three, which is how balanced 240 V and three-phase loads should be accounted for.
Does this replace a formal panel schedule on the drawings?
It produces the same load-balancing analysis and circuit directory you would document, but the official construction record should follow your jurisdiction's format and be verified against the installed panel directory and breaker ratings.